(a) a fence at least 2.4 m in height constructed of wire chain links made of wire not smaller than gauge number 11, having openings whose sides do not exceed 6 cm in length, and topped with at least three strands of barbed wire or barbed tape installed parallel to the fence on brackets angled outward;
(b) a wall at least 2.4 m in height, including any wall that forms part of a building, constructed of steel, wood, concrete, masonry or other substantial material or composites of such materials and, if it does not form part of a building, topped with at least three strands of barbed wire or barbed tape installed parallel to the wall on brackets angled outward; or
(a) the following elements, namely,
(iii) a separation of not less than 5 m between the two fences that is free of obstructions, other than guard posts, vehicle portals and intrusion detection and assessment devices; or
(5) The interior fence referred to in subparagraph (3)(a)(ii) is considered to be the perimeter of the protected area.
(6) Each gate, door, window or other means of entry or exit in the barrier shall be constructed so that it can be closed and locked.
(7) Those means of entry or exit shall be kept closed and locked except when persons or land vehicles are entering or exiting the protected area under the direct visual surveillance of a nuclear security officer.
History of the ActShow the text in English and French, side by side
Unofficial reproduction of the consolidated text published by the Department of Justice Canada, permitted by the Reproduction of Federal Law Order. Only the official text is authoritative.